Leakator® 10

A multi-purpose, hazardous location-certified combustible gas leak detector
  • Detects all combustible gases with excellent sensitivity and no calibration required
  • Sensor located in the probe tip for ultimate sensitivity, fast response and easy changing
  • Visual and audible indicators include an ultra-bright LED scale and a speaker (with earphone option)
Acetone, Acetylene, Benzene, Butane, Ethanol, Ethylene oxide, Gasoline, Hexane, Hydrogen, Industrial solvents, Methane, Paint thinners, Propane, Natural gas, Naptha, Combustible gases, Hydrocarbons

The Leakator® 10 is an ideal instrument for pinpointing combustible gas leaks in a number of residential, commercial and industrial applications, including gas pipeline surveying and valve, regulator and gas meter inspection. It uses a long-life (5 years typical) sensor and is easy to operate with one hand, giving you a reliable, easy-to-use tool.

The Leakator® 10 has a long, flexible neck for detecting leaks in hard-to-reach areas, bright LED scale to show relative leak sizes and a manual balance feature for finding leaks in backgrounds where target gas is present. It is UL 913 certified for hazardous locations, and carries a 1 year warranty that includes the sensor.

Gases Detected

All hydrocarbons/combustible gases, including but not limited to: acetone, acetylene, benzene, butane, ethanol,  gasoline, hexane, hydrogen, industrial solvents, methane, naptha, natural gas, paint thinners and propane

Sensitivity

20 ppm methane

Response Time

< 3 seconds to full scale indication

Leak Indicators

Visual (10 ultra-bright red LEDs) and audible (via internal speaker or optional earphone)

Automatic Background Adjustment

No (manual)

Power

5x C batteries

Run Time

30 hours typical (alkaline batteries)

Size (H x W x D)

Unit: 8.5 x 3.5 x 1.75 in. (21.6 x 8.9 x 4.4 cm)

Probe: 20 in. (50.8 cm)

Weight

12 oz (340 g) w/out batteries

Sensor Life

5 years (typical)

Operating Conditions

23 to 130 °F (-5 to 54 °C), 10 to 85% RH (non-condensing), 1 ATM

Warm-up Time

1 minute (approximate)

Approvals

CE mark

UL 913 Class 1, Division 1, Groups A, B, C & D

Warranty

1 year (including sensor)

 

Part Number

Description

0019-7051

Leakator® 10 (for all combustibles) with instruction manual and hard carrying case

Part Number

Description

 

0019-0398

Replacement sensor (combustibles)

0051-2529

Earphone (mono)